Resources · Articles · Inspection & Prevention

Fire department inspections vs. inspections by a fire protection contractor: who checks what, and when

July 15, 2019Inspect Point

Two different people inspect a commercial building for fire safety, and building owners mix them up all the time. The fire department, through the fire marshal or a fire inspector, inspects the building against the fire code on behalf of the Authority Having Jurisdiction (AHJ). A fire protection contractor inspects and tests the building's fire protection systems under the NFPA standards, on a schedule those standards set. Both produce a report. Neither replaces the other. This article covers what each one looks for, who performs it, how often it happens, and how the two reports fit together.

The fire department inspection: the building against the code

A fire department inspection is a code enforcement visit. The inspector walks the building with the adopted fire code and the Life Safety Code in hand and looks for hazards to occupants and to the firefighters who would respond to an emergency there. The list is broad and it is about conditions, not equipment tests:

  • Exits and egress: exit doors that open, corridors and stairs kept clear, exit signs and emergency lighting working, panic hardware where the code requires it.
  • Housekeeping and storage: combustible storage, clearance below sprinkler heads, flammable liquids handled and stored to code, electrical hazards.
  • Occupancy: the building used as permitted, occupant loads respected, fire lanes and hydrant access clear.
  • Records: current inspection and testing reports for the sprinkler, alarm, extinguisher, and suppression systems, produced by the contractor and kept by the owner.

That last item is where the two inspections meet. The fire inspector does not flow the sprinkler system or trip the alarm panel. They ask for the report that shows qualified people did, and they cite the owner when the report is missing or expired.

How often the fire department comes depends on the jurisdiction and the occupancy. High-hazard and high-occupancy buildings, such as schools, hospitals, and assembly occupancies, are typically inspected every year or more often. Small business occupancies may see an inspector every few years, or only when a complaint, a permit, or a change of occupancy triggers a visit. Some jurisdictions run self-inspection programs for low-hazard businesses.

The contractor inspection: the systems against the standards

A fire protection contractor's inspection is inspection, testing, and maintenance (ITM) of the systems themselves. The standards set the schedule and the method:

  • Fire alarm systems under NFPA 72: the panel, power supplies, initiating devices, notification appliances, and interfaces, most on an annual cycle with some items semiannual and some on longer rotations.
  • Water-based systems under NFPA 25: sprinklers, standpipes, fire pumps, and backflow assemblies, with items due weekly, monthly, quarterly, annually, and every five years. The frequency chart lays these out.
  • Portable extinguishers under NFPA 10: a monthly visual check, annual maintenance, and internal examination and hydrostatic testing on multi-year intervals.
  • Kitchen and special hazard suppression under NFPA 17, 17A, 2001, and 12, typically semiannual.
  • Fire door assemblies under NFPA 80, annually.

The contractor's technicians are qualified under the standard for the system they work on, which usually means a state license for the company and certifications such as NICET for the technicians. The result is a report per system, per visit, listing what was inspected, what was tested, what failed, and what was done about it. Deficiencies go to the owner in writing. Impairments, where a system is out of service, are reported to the AHJ as well.

Who is responsible for what

The building owner is responsible for both. The fire code requires the owner to maintain the building and its systems and to keep the ITM records available. The owner hires the contractor, schedules the work, and holds the reports. The fire department enforces; the contractor performs and documents. A building can pass its fire department inspection and still have a sprinkler system that has not been tested in two years, if nobody asked for the report. It can also have perfect ITM records and fail the fire department inspection for a chained exit door.

When each inspection happens

Fire department inspectionContractor ITM
Who performs itFire marshal or fire inspector, on behalf of the AHJA qualified service provider, or qualified in-house staff where licensing and the AHJ allow it
What it coversThe building's compliance with the fire code and Life Safety CodeThe fire protection systems, tested to the NFPA standard for each
How oftenSet by the jurisdiction and the occupancy; annual for high-hazard and high-occupancy buildings, less often for othersSet by the standards: weekly to five-year items, with the annual as the anchor
What you getAn inspection report with violations and a correction deadlineAn ITM report per system with results, deficiencies, and impairments
What happens on a failureA notice of violation, a reinspection, and in serious cases an order to vacateA deficiency to correct, a proposal for the repair, and an impairment procedure if the system is down

How the two reports work together

The fire inspector's visit goes better when the ITM reports are current, complete, and easy to find. The most common failures are not dramatic: an alarm report that is fourteen months old, a sprinkler report that lists the system as inspected but does not show the five-year internal, a deficiency from last year's report with no record of the repair. A contractor who keeps every inspection on the building's record, with deficiencies tracked to resolution, is doing the owner's compliance paperwork for them.

Many jurisdictions now want the contractor's reports submitted through a compliance portal such as The Compliance Engine, IROL, or LivSafe, so the AHJ has the report before the inspector arrives. That changes the fire department visit from a records check into a spot check.

Where Inspect Point fits

Inspect Point is the contractor's side of this. The forms follow the NFPA standard and code year the AHJ enforces, the inspection lives on the building's record with its deficiencies and proposals, and results sync to The Compliance Engine, IROL, and LivSafe so the report is in the AHJ's hands when they ask for it. The inspections feature page shows how the forms and the device list work. For the relationship with the AHJ itself, see working with the Authority Having Jurisdiction.

Common questions

Can the fire department inspect my fire alarm or sprinkler system?

The inspector can look at it and ask for the test records, and can witness a test. Performing the ITM is the owner's responsibility under the standards, carried out by a qualified service provider or by qualified in-house staff where the state and the AHJ allow it, and the inspector will expect the report either way.

Does a passed fire department inspection mean my systems are compliant?

No. It means the building met the code on the day of the visit, including having the records the inspector asked for. System compliance comes from the ITM schedule being kept.

Do I need a contractor if the fire department inspects every year?

The ITM still has to happen. Most owners use a licensed contractor; some larger owners use qualified in-house staff where the jurisdiction allows it. The fire department visit and the ITM are different events with different scopes, and the visit depends on the ITM report existing.